liquavision menu
Features : Systems : Cross Section : Set up : Spec Sheet : Datalogger


LIQUAVISION 8 SET UP STEPS

 


Let's say your tank is 100 inches deep, and the transducer you're using has a manufacturer's range of 0-150 inches of water column (INWC). The level sensor or end of the bubbler tube is located 10 inches off the bottom of the tank. With 15 inches of water in the tank you are cavitating the pump, and at 80 inches of water you are facing probable flooding. Your goal is to maintain a liquid level between 40 and 65 inches using LiquaVision®.


Taking the following steps while programming LiquaVision will maintain the range of liquid between 40 and 65 inches. High Alarm output circuit will be activated at 75 inches and the Low Alarm will be activated at 25 inches. The cross-section "window" into your tank that is displayed in the vertical Bar Graph will be from 10 to 90 inches.

1
Press SELECT; see RANG displayed, followed by a flashing R___; enter 150 inches for Transducer Range by using the INCREASE / DECREASE buttons.
This is the manufacturer setting printed on the transducer
2

Press SELECT; see OFST displayed,
followed by a flashing L___; enter 10 inches as the Offset or End of the Bubbler Pipe from the bottom of the tank.
3
Press SELECT; see P___; enter 90 inches as the Upper Limit in Display Window.
4
Press SELECT; see P___; enter 10 inches as the Lower Limit in the Display Window.

5
Press SELECT; see P___; enter 75 inches as the High Level Alarm/Fault level.
6
Press SELECT; see P___; enter 65 inches as the Make-Up OFF point, the highest level in the operating range.
7
Press SELECT; see P___; enter 40 inches as the Make-Up ON point, the lowest level in the operating range.
8
Press SELECT; see P___; enter 25 inches as the Low Level Alarm/Fault level.
  Press the ESC button after you have entered all of the set points. You're finished, and will return to operating mode.